(220-240V ~ 50Hz & 208-230V ~ 60Hz)
model | GMV-80WL/C-T | GMV-100WL/C-T | GMV-121WL/C-T | GMV-141WL/C-T | GMV-160WL/C-T | ||
Capacity Range | HP | 3 | 3.5 | 4 | 5 | 6 | |
Cooling Capacity | Nominal | Kw | 8 | 10 | 12.1 | 14.1 | 16 |
Heating Capacity | Nominal | Kw | 6 | 8 | 9 | 10 | 11.7 |
Max. | Kw | 9 | 11 | 13 | 16 | 18 | |
Seer | Channel | – | 7.0 | 6.6 | 7.2 | 6.76 | 7.82 |
Cassette | – | 7.0 | 6.6 | 6.10 | 6.69 | 7.07 | |
SCOP | Channel | – | 3.8 | 3.8 | 4.38 | 3.69 | 4.45 |
Cassette | – | 3.8 | 3.8 | 4.38 | 3.92 | 4.37 | |
Insurance Current | A | 25 | 25 | 32 | 40 | 40 | |
Power source | V / Ph / Hz | 220-240V ~ 50Hz & 208-230V ~ 60Hz | |||||
Max. Number of Connectable Internal Units | unit | 4 | 5 | 6 | 8 | 9 | |
Coolant Fluid Amount | Kg | 1.8 | 1.8 | 2 | 3.3 | 3.3 | |
Volume Power Level | dB(A) | 68 | 69 | 72 | 75 | 72 | |
Copper Pipe Connection | Liquid | Mm | Φ9.52 | Φ9.52 | Φ9.52 | Φ9.52 | Φ9.52 |
Gas | Mm | Φ15.9 | Φ15.9 | Φ15.9 | Φ15.9 | Φ19.05 | |
Outdoor Unit Size (G×D×Y) | Net | Mm | 980×360×790 | 980×360×790 | 980×360×790 | 940×460×820 | 900×340×1345 |
Package | Mm | 1097×477×937 | 1097×477×937 | 1097×477×937 | 1023×563×973 | 998×458×1500 | |
Net Weight / Gross Weight | Kg | 80/90 | 80/90 | 85/95 | 85/95 | 112/123 |
(380-415V 3N~50/60Hz)
model | GMV-120WL/C-X | GMV-140WL/C-X | GMV-160WL/C-X | ||
Capacity Range | HP | 4 | 5 | 6 | |
Cooling Capacity | Nominal | Kw | 12.1 | 14 | 16 |
Heating Capacity | Nominal | Kw | 11.7 | 11.91 | 11.7 |
Max. | Kw | 14 | 16.5 | 18 | |
Seer | Channel | – | 8.2 | 8.12 | 7.82 |
Cassette | – | 7.21 | 7.22 | 7.07 | |
SCOP | Channel | – | 4.45 | 4.45 | 4.45 |
Cassette | – | 4.38 | 4.37 | 4.37 | |
Insurance Current | A | 16 | 16 | 16 | |
Power source | V / Ph / Hz | 380-415V 3N~50/60Hz | |||
Max. Number of Connectable Internal Units | unit | 7 | 8 | 9 | |
Coolant Fluid Amount | Kg | 3.3 | 3.3 | 3.3 | |
Volume Power Level | dB(A) | 72 | 72 | 72 | |
Copper Pipe Connection | Liquid | Mm | Φ9.52 | Φ9.52 | Φ9.52 |
Gas | Mm | Φ15.9 | Φ15.9 | Φ19.05 | |
Outdoor Unit Size (G×D×Y) | Net | Mm | 900×340×1345 | 900×340×1345 | 900×340×1345 |
Package | Mm | 998×458×1500 | 998×458×1500 | 998×458×1500 | |
Net Weight / Gross Weight | Kg | 122/133 | 122/133 | 122/133 |
(380-415V 3N~50/60Hz)
model | GMV-224WL/C-X | GMV-280WL/C1-X | GMV-335WL/C1-X | ||
Capacity Range | HP | 8 | 10 | 12 | |
Cooling Capacity | Nominal | Kw | 22.4 | 28.0 | 33.5 |
Heating Capacity | Nominal | Kw | 16.5 | 18.0 | 21.5 |
Max. | Kw | 24.0 | 28.0 | 33.5 | |
Seer | Channel | – | 7.27 | 7.31 | 7.87 |
Cassette | – | 7.27 | 6.87 | 6.83 | |
SCOP | Channel | – | 4.08 | 5.19 | 5.50 |
Cassette | – | 4.11 | 4.66 | 5.21 | |
Insurance Current | A | 17.20 | 22.5 | 24.5 | |
Power source | V / Ph / Hz | 380-415V 3N~50/60Hz | |||
Max. Number of Connectable Internal Units | unit | 13 | 17 | 20 | |
Coolant Fluid Amount | Kg | 5.5 | 7.1 | 8.5 | |
Volume Power Level | dB(A) | 77 | 80 | 81 | |
Copper Pipe Connection | Liquid | Mm | Φ9.52 | Φ9.52 | Φ12.7 |
Gas | Mm | Φ19.05 | Φ22.2 | Φ25.4 | |
Outdoor Unit Size (G×D×Y) | Net | Mm | 940×320×1430 | 940×460×1615 | 940×460×1615 |
Package | Mm | 1038×438×1580 | 1038×578×1765 | 1038×578×1765 | |
Net Weight / Gross Weight | Kg | 133/144 | 163/175 | 174/187 |
1. Test requirements for measured values; cooling outdoor air 35°CKT, indoor 27°CKT/19°CYT, outdoor air 7°CKT/6°CYT in heating, indoor temperature 20°CKT, copper piping distance 5m and units
There is no difference in height between them.
2. The total connectable indoor unit capacity must be between 50% and 135% of the outdoor unit capacity. Correction tables are available for the desired capacity based on variable parameters.
3. Outdoor unit operating temperature range is -5~52°C for cooling and -20~27°C for heating.