model | FDC112KXZEN1 | FDC140KXZEN1 | FDC155KXZEN1 | FDC112KXZES1 | FDC140KXZES1 | FDC155KXZES1 | |||
Nominal Horsepower | 4HP | 5HP | 6HP | 4HP | 5HP | 6HP | |||
Energy Supply | 1 Phase 220-240V, 50Hz | 3 Phase 380-415V, 50Hz | |||||||
Nominal Capacity | Cooling | Kw | 11,2 | 14,0 | 15,5 | 11,2 | 14,0 | 15,5 | |
heating | 12,5 | 16,0 | 16,3 | 12,5 | 16,0 | 16,3 | |||
Electrical Properties |
Starting Current | A | 5 | ||||||
Power Consumption | Cooling | Kw | 2,52 | 3,96 | 5,20 | 2,52 | 3,96 | 5,20 | |
heating | 2,57 | 3,66 | 4,28 | 2,57 | 3,66 | 4,28 | |||
Operating Current | Cooling | A | 13.5 – 12.4 | 20.6 – 18.9 | 23.3 – 21.3 | 4.5 – 4.1 | 6.9 – 6.3 | 7.8 – 7.1 | |
heating | 14.1 – 12.9 | 21.5 – 19.7 | 21.9 – 20.1 | 4.7 – 4.3 | 7.2 – 6.6 | 7.3 – 6.7 | |||
Eer | Cooling | 4,44 | 3,54 | 2,98 | 4,44 | 3,54 | 2,98 | ||
COP | heating | 4,36 | 3,83 | 3,62 | 4,86 | 4,37 | 3,81 | ||
Seer | standard | – | 7,73 | 7,21 | – | 7,73 | 7,21 | ||
External Dimensions | YxGxD | Mm | 845x970x370 | ||||||
Net Weight | Kg | 85 | 87 | ||||||
Coolant Fluid Amount | R410A | Kg | 5,0 | ||||||
Volume | Cooling / Heating | dB(A) | 52/55 | 53/57 | 54/57 | 52/55 | 53/57 | 54/57 | |
Refrigerant PipeWork | Liquid Line | mm(in) | ø9.52(3/8") | ||||||
Gas Line | ø15.88(5/8") | ||||||||
Capacity Connection Range | % | 80~150 | |||||||
Number of Connectable Internal Units | 8 | 10* | 8 | 10* |
- The Micro KXZ heat pump 2-pipe system offers high performance for VRF applications requiring heating only or cooling alone; Ideal for a wide range of applications.
- 10* internal units and up to 150% capacity connection.
- EER values up to 4.44 with high efficiency. (In cooling)
- Micro KXZ only has a DC inverter compressor.
- It has superior piping limits with total piping up to 100 m and a maximum pipe length of 70 m.